CAD (0)
  • Cart is empty
TeSys D IEC Contactor - 40A - 208Vac Coil
Unit of Measure

Termination Method

N/A Spring Clamp

Contact Rating

N/A 600V / 40A

Coil Voltage

N/A 208Vac 50/60 Hz

50/60 Hz Voltage Code

N/A LE7

Coil Consumption Inrush

N/A 140 VA

Coil Consumption Sealed

N/A 13 VA

Power Wire Size

N/A #2 - #16 AWG

Power Terminal Torque

N/A 70 lb-in (8 Nm)

Control Wire Size

N/A #12 - #20 AWG

Control Terminal Torque

N/A N/A

Mounting Hardware

N/A 35mm DIN Rail, #8 screw

Weight

N/A 0.85 lb (0.385 kg)

AC1 Resitive Rating

N/A 60 Amp

AC3 Inductive Rating

N/A 40 Amp

AC3 Single Phase 115V

N/A 3 HP

AC3 Single Phase 230V

N/A 5 HP

AC3 Three Phase 200V

N/A 10 HP

AC3 Three Phase 230V

N/A 10 HP

AC3 Three Phase 460V

N/A 30 HP

AC3 Three Phase 575V

N/A 30 HP

Control Contact Rating (1NC/0NO)

N/A A600

UL File/CCN

N/A E164862 / NLDX

CSA File

N/A LR43364 3211 04

Meets Standard

N/A IEC 60647-4

CE

N/A Yes

RoHS

N/A Yes