CAD (0)
  • Cart is empty
Unit of Measure

Output Type 

N/A 3 NO Relay Instantaneous opening potential free

Control Voltage

N/A 24 VDC

Max PLd level per EN/ISO 13849-1

N/A PLd/Category 4

Max SIL level per EN/IEC 61508 and EN/IEC 62061

N/A SILCL3

Diagnostic Coverage per ISO/EN 13849-1:2008

N/A 0.95

Certifications

N/A TÜV, RCM, EAC, UL 61010-2-201 (CSA pending), ANSI, CSA C1D2 pending

Terminal Type 

N/A Spring

Marking

N/A CE, CSA, UL, EFUP 10, REACH, TÜV, EAC, RCM

SFF Per IEC 61508-1

N/A 0.95

PFHd IEC/EN 61508-1:2010 60 cycles per hour at DC-13 24 Vdc 1 A

N/A 30 * 10^-9 / h

PFHd IEC/EN 61508-1:2010 1 cycle per hour at DC-13 24 Vdc 4 A

N/A 5 * 10^-9 / h

MTTFd per EN/ISO 13849-1 at 60 operations/hour DC-13 24 V DC 1 A

N/A 85 years

MTTFd per EN/ISO 13849-1 at 1 operation/hour DC-13 24 V DC 4 A

N/A 500 years

HFT per IEC 61508-1

N/A 1

Standards

N/A EN 1088/ISO 14119, EN 60204-1, EN/IEC 60947-1, EN/IEC 60947-5-1, EN/ISO 13850

Operating Temperature

N/A -10 to 55 °C horizontal Installation

Storage Temperature

N/A -25 to 70 °C

Relative humidity

N/A 10% to 95% without condensation

Protection

N/A IP20 EN/IEC 60529 terminals

RoHS

N/A Yes